Intumesent Pipe Wraps


INTUMESCENT PIPE WRAPSUp to 4 hours protection |
INTRODUCTION Intumescent pipe wraps offer a low cost, easily installed alternative to DESCRIPTION Based on a graphite intumescent This fibre-reinforced material exhibits an excellent resistance to erosion and enables extended periods of fire resistance to be achieved. Its intumescent reaction commences at 190°C with low smoke emission and no halogen by-products from combustion being produced. The pipe wrap utilises several layers of intumescent mat dimensioned to suit the pipe diameter, backed with a pvc tape and fitted with self-adhesive togs for fastening. They are resistant to water and most liquids commonly found in the building environment. |
INSTALLATION Intumescent pipewraps are simply wrapped around the circumference of the pipe to be protected and the ends joined with the self-adhesive tag. It is then moved along the pipe to a position within the floor slab 12mm from the underside; or centrally within a wall but no more than 52mm from each side. |
PERFORMANCE Intumescent pipe wraps have been Tested to European Standard BSEN 1366-3
|
||||||||||
|
||||||||||||