FIROBLOK INTUMESCENT FLEXIBLE WRAPS

Wraps, sleeves for ducting, pipes and electrical trunking

 
Download datasheet

DESCRIPTION

Firoblok sleeves are designed to protect cables and metal/plastic pipes and ventilation trunking passing through fire-rated ceilings, floors, or walls made from block, brick, or concrete, and hollow plasterboard floors and walls. They are flexible, allowing contraction and expansion of water pipes, and give protection from corrosion caused by close contact with cement, cement blocks, plaster, and other corrosive building materials.

A silver coloured reinforced covering contains the intumescent material so that it expands inwards and crushes into melting PVC pipes, trunking, ducts, etc in the heat of a fire. They also absorb heat from fire and help prevent metal pipes, services, and armoured cables from overheating.

The sleeves are supplied in 100mm, 150mm, 200mm, or 500mm lengths. They can be easily cut with a sharp knife and they should be installed level with the surrounding ceiling, floor, or wall. In the case of a fire, the intumescent material will expand, sealing the gap between the cable or pipe and its surrounding ceiling or wall. See also Product 7 (intumescent wraps) and Product 25 (cable protection system for cavity walls).

USE

For services passing through fire-rated ceilings and walls (especially where contraction and expansion allowance is required, e.g. water/gas pipes). Also for use in brick, block, concrete, and hollow floors or walls.

PERFORMANCE

This product underwent a fire resistance test employing the general procedures and criteria of BS476 Part 22 (1987), achieving an integrity of 130 minutes in solid walls, 67 minutes in hollow walls, and 4 hours in concrete/ block ceilings/walls. Also tested to EN1366-3 (2005), EN1363-1 (2000), and EN13501-2 (2004)

PREPERATION FITTING GUIDE

Firoblok Fitting 1   Firoblok Fitting 2
Measure the depth of the opening and mark this on the wrap. You cut off just what you need with no waste.   Cut the wrap to the marked depth with a sharp knife.
Firoblok Fitting 3   Firoblok Fitting 4
Lift the self-adhesive flap to reveal a marked line along the depth of the wrap.   Cut along the marked line with a sharp knife to open up the wrap for fitting onto the trunking or ducting.
Firoblok Fitting 5   Firoblok Fitting 6
Check that the wrap fits comfortably
around the trunking and introduce this combination into the opening.
  Whilst holding the wrap in place, remove the backing from the self - adhesive strip.
Firoblok Fitting 7   Firoblok Fitting 8
Firmly fasten the self-adhesive strip over the join of the wrap.   Finally, push the wrap into the opening until it is level with the surface.

ORDERING REFERENCES

For Cables, Pipes and Trunking
Reference Internal Diameter External Diameter
IWS 18
18mm
26mm
IWS 25 25mm 30mm
IWS 33 33mm 45mm
IWS 40 40mm 50mm
IWS 50 50mm 59mm
IWS 55 55mm 65mm
IWS 60 60mm 75mm
IWS 83 83mm 97mm
IWS 90 90mm 105mm
IWS 100 100mm 116mm
IWS 115 115mm 131mm
IWS 150 150mm 170mm
IWS 165 165mm 189mm
IWS 215 215mm 265mm

SOLID FIXING

Solid Fitting 1   Solid Fitting 2
Product 110 shown in a concrete floor
construction.
  For walls classed as a risk on one side only, cut the sleeve to size and place on risk side.
Solid Fitting 3   Solid Fitting 1
IWS sleeves can be fitted through walls for protection from both sides. Sleeves for cables require a
protective insert (IWS/C) to prevent puncture. Smoke
seal plates are also available.
  A square sleeve can be supplied for cable
trunking protection.
HOLLOW FIXING

Hollow Fixing 3

Fixing plates must be used in wooden floors.

 

Hollow Fixing 2

Hollow Fixing 1

    The IWS sleeves can be fitted through hollow plasterboard walls. Sleeves used for cables require a protective insert (IWS/C) to prevent puncture.


Ventilation Ducting (mm) Plastic Electrical Trunking (mm)
Reference Size Reference Size
110V/15 110 x 54
110T/11 25 x 25
110V/26 204 x 60 110T/22 50 x 50
I110V/29 220 x 90 110T/33 75 x 75
110V/22 234 x 29 110T/32 75 x 50
110V/32 308 x 29 110T/42 100 x 50
110V/67 692 x 70 110T/43 100x75
  110T/44 100 x 100
 
Both types are available in 100mm, 150mm, 200mm, and 500mm lengths.