SLOTGRILLE

Up to 60 minutes fire resistance


 
Download datasheet

INTRODUCTION

Ventilation and air conditioning ducts that penetrate fire separating elements need to have their integrity maintained. This also applies to fire resisting doors that require the passage of free air through them, such as doors to boiler rooms.

Slotgrille air transfer grilles can provide up to 60 minutes integrity and insulation in accordance with BS 476 Part 22 1987, but still allow 60% free air flow in normal use.

DESCRIPTION

Slotgrilles are manufactured from
horizontal slats of high performance intumescent spaced 16mm apart. 38mm thick units provide up to 60 minutes fire resistance.

Slotgrille

Circular Slotgrilles are available in standard sizes of 100mm, 125mm, 150mm and 200mm.

 

 

Circular Slotgrille

INSTALLATION

Fire resisting doors and partitions

Slotgrille units can be fixed into fire resisting doors or timber stud partitions using a hardwood or steel flange. Alternatively wood screws can be used through the perimeter of the units.

Gaps around the Slotgrille unit
greater than 3mm should be fire
sealed using an intumescent sealant.

Ventilation Ducts

Slotgrille dampers must be
secured within the ducting using
4 self tapping screws. On circular
Slotgrille the screws should
pass through the aluminium rings
on the outer part of the Slotgrille. Clearance gaps should be sealed using an intumescent sealant

FINISHES

Standard colour white.

Non standard colours red and
bronze.

COVER PLATES

Optional cover grilles for walls, doors and ends of ducts pressed steel and aluminium options available.

Cover Plates

 

MAINTENANCE

Since there are no moving parts
to go wrong, Slotgrilles are easily maintained. Units should be cleaned using a damp cloth. Grease can be removed by using
neat liquid detergent or methylated spirit. Strong degreasing agents should not be used nor should the units be immersed or saturated with water.

ORDERING

Slotgrilles can be ordered by contacting our sales department. When ordering please state, fire
resistance required, width, height
and colour.

Slotgrille Integrity (mins) Insulation (mins)
Warrington
C67719/A/C
36 36
Warrington
C67719/A/E
46 46
Warrington
C67719/A/P1
66 66
Warrington
C67719/A/P2
66 66
Warrington
103908
90 75
Warrington
C106643
V* V*
TNO 08.20.6.
7198/539
66 66
TRADA IT284/E1 31 31
TRADA IT285/C1 66 66

* V = Various

STANDARD SIZES AVAILABLE

100X100X38MM
150X150X38MM
200X200X38MM
200X150X38MM
225X75X38MM
250X250X38MM
300X150X38MM
300X300X38MM
350X350X38MM
400X400X38MM
500X500X38MM
600X600X38MM

Other sizes available up to a maximum of 600x600x38mm.