Therm-A-Glaze 30
See also Therm-A-Glaze 60
THERM-A-GLAZE 30Protection for glazing panel and timber beading |
INTRODUCTION Intumescent fire seals are an essential element of a glazing panel in a timber fire door set designed to meet the criteria of BS 476: Parts 20 and 22: 1987. To meet this requirement APPLICATION THERM-A-GLAZE has been developed to provide protection to the glazing panel and timber beading. A strip 10mm x 2mm located between the beads and the glass will provide fire resistant protection in an FD 30 or FD 30S timber fire door when suitable beading has been used. THERM-A-GLAZE can be used without additional protection from moisture or other atmospheric |
and its self adhesive backing ensures a simple but reliable method of fixing to the timber beading. THERM-A-GLAZE can be used to protect 6mm Georgian wired glass in apertures up to 900mm x 600mm. DESCRIPTION THERM-A-GLAZE is manufactured to a unique chemical formulation based on expandable graphite. The flexible strip is inherently resistant to water and normal environmental conditions so that no external protection is required. TEST EVIDENCE Test evidence is available on request. AVAILABILITY THERM-A-GLAZE is supplied as a self adhesive strip 10mm x 2mm (other sizes available) and in standard lengths of 2100mm. |
|